CVE-2013-2796Date: (C)2013-08-14   (M)2023-12-22


Schneider Electric Vijeo Citect 7.20 and earlier, CitectSCADA 7.20 and earlier, and PowerLogic SCADA 7.20 and earlier allow remote attackers to read arbitrary files, send HTTP requests to intranet servers, or cause a denial of service (CPU and memory consumption) via an XML document containing an external entity declaration in conjunction with an entity reference, related to an XML External Entity (XXE) issue.

CVSS Score and Metrics +CVSS Score and Metrics -

CVSS V2 Severity:
CVSS Score : 6.9
Exploit Score: 3.4
Impact Score: 10.0
 
CVSS V2 Metrics:
Access Vector: LOCAL
Access Complexity: MEDIUM
Authentication: NONE
Confidentiality: COMPLETE
Integrity: COMPLETE
Availability: COMPLETE
  
Reference:
http://ics-cert.us-cert.gov/advisories/ICSA-13-217-02
http://www.citect.schneider-electric.com/cs-HF720SP459363

CPE    4
cpe:/a:schneider-electric:citectscada:7.10
cpe:/a:schneider-electric:vijeo_citect:7.10
cpe:/a:schneider-electric:powerlogic_scada:7.10
cpe:/a:schneider-electric:citectscada
...
CWE    1
CWE-264