CVE-2020-11999 | Date: (C)2020-06-16 (M)2023-12-22 |
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to specify a filename to execute unauthorized code and modify files or data.
CVSS Score and Metrics +CVSS Score and Metrics -CVSS V3 Severity: | CVSS V2 Severity: |
CVSS Score : 8.1 | CVSS Score : 5.5 |
Exploit Score: 2.8 | Exploit Score: 8.0 |
Impact Score: 5.2 | Impact Score: 4.9 |
|
CVSS V3 Metrics: | CVSS V2 Metrics: |
Attack Vector: NETWORK | Access Vector: NETWORK |
Attack Complexity: LOW | Access Complexity: LOW |
Privileges Required: LOW | Authentication: SINGLE |
User Interaction: NONE | Confidentiality: PARTIAL |
Scope: UNCHANGED | Integrity: PARTIAL |
Confidentiality: HIGH | Availability: NONE |
Integrity: HIGH | |
Availability: NONE | |
| |