CVE-2018-13814 | Date: (C)2018-12-17 (M)2023-12-22 |
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V14), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V14), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V14), SIMATIC WinCC Runtime Advanced (All versions < V14), SIMATIC WinCC Runtime Professional (All versions < V14), SIMATIC WinCC (TIA Portal) (All versions < V14), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The integrated web server (port 80/tcp and port 443/tcp) of the affected devices could allow an attacker to inject HTTP headers. An attacker must trick a valid user who is authenticated to the device into clicking on a malicious link to exploit the vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVSS Score and Metrics +CVSS Score and Metrics -CVSS V3 Severity: | CVSS V2 Severity: |
CVSS Score : 8.8 | CVSS Score : 6.8 |
Exploit Score: 2.8 | Exploit Score: 8.6 |
Impact Score: 5.9 | Impact Score: 6.4 |
|
CVSS V3 Metrics: | CVSS V2 Metrics: |
Attack Vector: NETWORK | Access Vector: NETWORK |
Attack Complexity: LOW | Access Complexity: MEDIUM |
Privileges Required: NONE | Authentication: NONE |
User Interaction: REQUIRED | Confidentiality: PARTIAL |
Scope: UNCHANGED | Integrity: PARTIAL |
Confidentiality: HIGH | Availability: PARTIAL |
Integrity: HIGH | |
Availability: HIGH | |
| |